The Breakdown Voltage of Moistened Mineral Oil During Its Cooling
- 1 September 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 29 (6) , 2181-2189
Abstract
In high voltage oil-filled equipment, mineral insulating oil has two main functions - to remove heat from heated parts and to insulate conductors. Regardless of the temperature, transformer oil must always provide reliable insulation of high-voltage equipment elements. The primary indicator characterizing the electrical insulating properties of mineral oil is its electrical strength. This work presents the results of the study, which reflect the change in the value of the breakdown voltage of the oil during its cooling from + 60 °C to -20 °C. Modeling shows that when the cell is cooled, together with its contents, conditions are realized on the electrodes for the predominant formation of water in the form of drops or ice particles. Such an experiment and simulation shows the processes occurring in the insulation of a power transformer during its forced commissioning and decommissioning at negative temperatures. Experimental data on the nature of changes in the breakdown voltage of a liquid dielectric depending on the cooling method and the degree of oil oxidation are presented. Ice crystals form in the oil as it cools, the shape of which is different. It was found that in the process of oil cooling in the interelectrode gap, an “ice cloud” or “ice bridge” is formed. During thawing, emulsion water is formed from ice inclusions, which are concentrated on the electrodes of the measuring cell. It was experimentally determined that under high voltage action in small gaps of the measuring cell, water droplets are drawn out, forming a "water bridge" between the electrodes.Keywords
Funding Information
- Ministry of Science and Higher Education of the Russian Federation (FSUN-2020-0012)
This publication has 25 references indexed in Scilit:
- Measuring the Pressboard Water Content of Transformers Using Cellulose Isotherms and the Frequency Components of Water MigrationIEEE Transactions on Power Delivery, 2016
- Investigation on Transient Oscillation of Droplet Deformation before Conical Breakup under Alternating Current Electric FieldLangmuir, 2015
- Dynamics of water droplets immersed in dielectric liquids submitted to electric stressIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- The resistivity of oil and oil-impregnated pressboard varies with temperature and electric field strengthIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Understanding moisture diffusion process in oil-impregnated pressboard insulation of transformer2011
- Modeling of transient moisture equilibrium in oil-paper insulationIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Water in oil-filled high-voltage equipment part II: water content as physicochemical tools for insulation condition diagnosticIEEE Electrical Insulation Magazine, 2007
- The temperature dependence of the dielectric strength of transformer oil and pressboard insulation at HVDC polarity reversal stress2003
- Fundamental investigations on some transformer liquids under various outdoor conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2001
- Moisture solubility for differently conditioned transformer oilsIEEE Transactions on Dielectrics and Electrical Insulation, 2001