Abstract
Many water systems are challenged with uncertainty regarding service line material type. This work investigated using a simple drinking water flushed sampling approach and a more complicated and invasive sequential profile sampling approach to predict whether homes had an existing lead service line (LSL). Homes that never had an LSL (control groups) and homes with LSLs (study groups) in two communities having different degrees of corrosion control were sampled. Using control groups' results, community‐specific “threshold” lead levels were determined and compared to results from study groups. The flushed sampling maximum lead concentration (FMC) of lead accurately predicted 100% and 60% of LSL sites for the community with poor and good corrosion control, respectively. The weighted average sequential profile lead concentration (WASLC) increased the 40% not identified as LSL sites by fully flushed samples to 100%. The WASLC closely followed by the maximum sequential profile lead concentration were most reliable in identifying LSLs.Keywords
Funding Information
- U.S. Environmental Protection Agency (EP‐C‐15‐010)
This publication has 28 references indexed in Scilit:
- Detection and Evaluation of Elevated Lead Release from Service Lines: A Field StudyEnvironmental Science & Technology, 2013
- Application of lead monitoring results to predict 0–7 year old children's exposure at the tapWater Research, 2013
- Lead (Pb) in Tap Water and in Blood: Implications for Lead Exposure in the United StatesCritical Reviews in Environmental Science and Technology, 2012
- Computational modelling to investigate the sampling of lead in drinking waterWater Research, 2009
- Blood Lead Below 0.48 μmol/L (10 μg/dL) and Mortality Among US AdultsCirculation, 2006
- Development of a convective diffusion model for lead pipe rigs operating in laminar flowWater Research, 2006
- Modelling the diffusion of lead into drinking waterApplied Mathematical Modelling, 2002
- Environmental lead exposure during early childhoodThe Journal of Pediatrics, 2002
- Causes of temporal variability of lead in domestic plumbing systemsEnvironmental Monitoring and Assessment, 1990
- A mass transfer model to describe lead concentrations in drinking waterWater Research, 1983