Motion and adsorption: dynamic characteristics and spatial distribution of metallic particle in dry air DC-GIS
- 29 September 2026
- journal article
- Published by IOP Publishing in Journal of Physics D: Applied Physics
- Vol. 59 (39) , 395502
Abstract
Metallic particles within gas-insulated switchgear (GIS) can distort electric fields, leading to gas discharge. Their adsorption onto insulator surface is particularly hazardous, as it can cause flashover and seriously compromise insulation safety. In this study, a transparent conductive scaled GIS busbar is used combined with an object detection model to investigate the motion and adsorption characteristics of linear metallic particle in dry air. Results show that, compared to SF 6 gas, the metallic particle in dry air exhibits higher velocity and a wider range of movement. However, it shows a lower probability of engaging in firefly motion and adsorbing onto insulator surfaces. Under positive polarity, the primary pattern is reciprocating movement. In contrast, under negative polarity, the particle exhibits prolonged swaying firefly motion on the conductor surface. Furthermore, increasing voltage enhances velocity and reduces the likelihood of firefly motion. Additionally, increasing the particle radius decreases firefly motion probability, whereas increasing length leads to the opposite result. Finally, the lifting position has no significant impact. This study supports suppressing metallic particle contamination and optimizing insulation design in dry air DC-GIS.Keywords
Funding Information
- Smart-Grid National Science and Technology Major Project (2025ZD0808300)
This publication has 22 references indexed in Scilit:
- Trends in High Voltage Switchgear Research and TechnologyIEEJ Transactions on Electrical and Electronic Engineering, 2024
- Microscopic characteristics of SF6 partial discharge induced by a floating linear metal particleApplied Physics Letters, 2024
- Optimization of insulators in ±550 kV HVDC GIS for offshore wind platform considering charge accumulationElectric Power Systems Research, 2023
- Particle behavior and trap design for ±320 kV gas-insulated power transmission line (GIL)Journal of Physics D: Applied Physics, 2023
- Computational analysis of electrical breakdown of SF6/N2 mixturesJournal of Applied Physics, 2023
- The flashover of epoxy initiated by micron metal particles under DC voltage: phenomenon and mechanismJournal of Physics D: Applied Physics, 2022
- Insulation degradation affected by micron metal particles attached on epoxy surface: charge accumulation and flashover voltageJournal of Physics D: Applied Physics, 2022
- Modelling on thermal‐fluid field in SF 6 insulated high voltage direct current bushing with its influence on electric field distribution and metal particle motionHigh Voltage, 2022
- Insulation characteristics of quasi-uniform electric field and effect of metallic particle contaminationin highly compressed dry airIET Conference Proceedings, 2022
- Research on discharge phenomenon caused by cross‐adsorption of linear insulating fibre and metal dust under DC voltageHigh Voltage, 2020