Study on decay‐like fracture of 500 kV composite insulators: Infrared, ultraviolet and electric field distribution detection
Authors:
Open Access
- 22 August 2022
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 16 (20) , 4132-4141
Abstract
The power outage caused by decay‐like fracture of composite insulators significantly impacts the power grid. In this paper, a decay‐like fractured insulator of 500 kV transmission line is taken as a research object. The detailed observation of core rod and silicone rubber housings, discharge results, temperature rises, and electric field distribution are obtained. (a) The fractured insulator has abnormal heating on the exposed core rod and sheath surface, and the ambient temperature and humidity significantly influence the temperature rise. (b) It is proposed that one of the most obvious characteristics of decay‐like insulator is abnormal temperature and temperature rise (such as T > 50°C, ΔT > 30 K). (c) Under the same conditions, temperature rises, electrical discharge, and electrical field strength of decay‐like insulator are higher than those of other insulators, and the discharge at the bare core rod is intense. (d) The electric field strength distribution and discharge distribution of decay‐like insulator are different from other aging and new insulators. However, the measurement results are significantly affected by test conditions. Therefore, it is difficult to determine whether the composite insulators are decay‐like using electric field distribution and UV measurement on site.Keywords
This publication has 21 references indexed in Scilit:
- Effect of moisture on temperature rise of composite insulators operating in power systemIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Mechanism of fracture related heating for 500-kV composite insulators in highly humid areasInternational Transactions on Electrical Energy Systems, 2015
- Failure analysis of decay-like fracture of composite insulatorIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- 50 years in the development of polymer suspension-type insulatorsIEEE Electrical Insulation Magazine, 2013
- Introduction2013
- Analysis of a fractured 500 kV composite insulator - identification of aging mechanisms and their causesIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Characterization of polymeric insulators using thermal and UV imaging under laboratory conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Impact of corona on the long-term performance of nonceramic insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2003
- Failure of high voltage electrical insulators with pultruded glass fibre-reinforced plastic coresComposites, 1986
- Metallographic investigation of the damage caused to GRP by the combined action of electrical, mechanical and chemical environmentsJournal of Materials Science, 1984