Analysis of influence of a novel inductive fault current limiter on the circuit breaker in 500 kV power system
Open Access
- 4 May 2021
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in High Voltage
- Vol. 6 (6) , 997-1008
Abstract
A contribution to the engineering application of a proposed 500 kV fault current limiter (FCL) is presented. A new type of FCL composed of a highly coupled split reactor (HCSR) and fast switches is proposed. When the circuit breaker (CB) in series with the FCL in the 500 kV power system interrupts the limited fault current, the rate of rise of the recovery voltage (RRRV) reaches a value much higher than the rated value. Based on a simplified equivalent single‐phase circuit, the influence of the new FCL on the interruption procedure of the CB is simulated and discussed. The simulation results show that the high RRRV is caused by high‐frequency resonant oscillations between the HCSR and its parasite capacitance. Analysis indicates that when the reactance of the FCL is close to the short circuit reactance of the system, the RRRV will reach the highest value. To solve this issue, we proposed installing a shunt capacitor with the FCL. Simulation results showed that the RRRV under all fault modes could be restrained to below the rated value by introducing a certain shunt capacitor.Keywords
This publication has 20 references indexed in Scilit:
- A New Structure of Fault Current Limiter Based on the System Impedance With Fast Eliminating Method and Simple Control ProcedureIEEE Transactions on Industrial Electronics, 2017
- Development and Analysis of Bridge-Type Saturated-Core Fault Current LimiterIEEE Transactions on Magnetics, 2017
- Interrupting Characteristics of Paralleled SF6Circuit Breakers With a Highly Coupled Split ReactorIEEE Transactions on Components, Packaging and Manufacturing Technology, 2017
- Distribution Network Protection Using Smart Dual Functional Series Resonance-Based Fault Current and Ferroresonance Overvoltage LimiterIEEE Transactions on Smart Grid, 2016
- A Novel Solid-State Fault Current-Limiting Circuit Breaker for Medium-Voltage Network ApplicationsIEEE Transactions on Power Delivery, 2015
- Terminal Faults2014
- Impact of the Inductive FCL on the Interrupting Characteristics of High-Voltage CBs During Out-of-Phase FaultsIEEE Transactions on Power Delivery, 2009
- Impact Research of Inductive FCL on the Rate of Rise of Recovery Voltage With Circuit BreakersIEEE Transactions on Power Delivery, 2008
- Interrupting condition imposed on a circuit breaker connected with fault current limiter2003
- Transient Recovery Voltages on Power Systems Part II - Practical Methods of DeterminationTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1958