Diagnosis Method of Decay-like Composite Insulators in a High-Humidity Environment Based on Characteristic Coefficient of Temperature Rise Gradient
Open Access
Abstract
At present, the temperature rise in insulators is observed using infrared thermometry as a common method of diagnosing decay-like insulators. However, the original characteristic data obtained by infrared thermometry cannot effectively distinguish some of the decay-like insulators from those with ageing sheaths. Therefore, it is imperative to find a new diagnostic characteristic quantity. Based on statistical data, this article first explains that existing diagnostic methods have limited diagnostic effectiveness and a high false detection rate for insulators in a slightly heated state. A full-scale temperature rise test is carried out on a batch of composite insulators returned from the field under high-humidity conditions. Two different defective insulators with similar temperature rise profiles are identified, and an electro-thermal coupling simulation model is developed based on the dielectric characteristic parameters of the above insulators for both core rod defects and sheath ageing. A new infrared diagnostic feature, the temperature rise gradient coefficient, is then obtained to identify the source of abnormal heat in insulators using statistical analysis of an infrared image gallery of abnormally hot composite insulators obtained from field inspections and laboratory tests.Keywords
Funding Information
- Natural Science Foundation of Hebei Province (E2021502025)
This publication has 7 references indexed in Scilit:
- Study on decay‐like fracture of 500 kV composite insulators: Infrared, ultraviolet and electric field distribution detectionIET Generation, Transmission & Distribution, 2022
- Defect Identification of Composite Insulator Based on Infrared ImagePolymers, 2022
- Study on the influence mechanism of ambient humidity on the temperature rise of decay‐like composite insulatorsHigh Voltage, 2021
- Temperature distribution characteristics and heat defect judgment method based on temperature gradient of suspended composite insulator in operationIET Generation, Transmission & Distribution, 2021
- Study on artificial multi‐stress ageing characteristics of composite insulatorsIET Generation, Transmission & Distribution, 2018
- An Optimized Infrared Detection Strategy for Defective Composite Insulators According to the Law of Heat Flux Propagation Considering the Environmental FactorsIEEE Access, 2018
- Failure analysis of decay-like fracture of composite insulatorIEEE Transactions on Dielectrics and Electrical Insulation, 2014