This article presents a new method based on the combination of digital signal processing parameters for the selection of optimal characteristics of corona discharges in HVDC systems, particularly for linearization of the discharge model for applications that require a simplified computational approach. The proposed method implements a new metric from the coefficient of variation, CVSTFT , based on the short-time Fourier transform (STFT) and the Hinkley criterion to measure the spectral variability and determine the corona discharge profile in different situations. An experimental analysis was performed by applying voltages between ± 30kV and ± 100 kV in a conductor, and electrical current signals proportional to the corona effect were collected through a data acquisition system. The results indicated that the application of the new method was successful in quantifying, in a simple way, the percentage of growth of corona discharges as a function of the voltage applied within the range of 40-80 kHz. Moreover, it showed 90 %, 91 %, 92%, 97%, 89%, 92%, and 93% of reliability in calculating the root-mean-square deviation (RMSD) based on approximation by a linear model. The frequency band resulting from this study proved to be favorable to establishing a threshold for the percentage of corona discharge growth according to its profile or condition of application, indicating this information may be useful in the construction of mobile devices with low consumption and computational performance, meeting the demands of Industry 4.0 and the Internet of Things.Keywords
Funding Information
- Interligação Elétrica do Madeira S.A.
- Agência Nacional de Energia Elétrica [Brazilian Electricity Regulatory Agency (ANEEL)] (PD-06957-0005/2020)
This publication has 24 references indexed in Scilit:
- Assessment of Macro Fiber Composite Sensors for Measurement of Acoustic Partial Discharge Signals in Power TransformersIEEE Sensors Journal, 2017
- Model, Design, and Testing of Field Mill Sensors for Measuring Electric Fields Under High-Voltage Direct-Current Power LinesIEEE Transactions on Industrial Electronics, 2017
- Identification of acoustic signals of corona discharges under different contamination levels using wavelet transformElectrical Engineering, 2017
- Analysis of HVDC superimposed harmonic voltage effects on partial discharge behavior in solid dielectric mediaIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Development of a sensor for corona current measurement under high-voltage direct-current transmission linesInternational Journal of Distributed Sensor Networks, 2016
- Design and Application of Corona Current Measurement System under High-Voltage Direct-Current Environment2015
- On-line monitoring of partial discharges in a HVDC station environmentIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Diagnostic of HVDC systems using partial dischargesIEEE Transactions on Dielectrics and Electrical Insulation, 2011
- Detection and location of partial discharges in power transformers using acoustic and electromagnetic signalsIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Online source recognition of partial discharge for gas insulated substations using independent component analysisIEEE Transactions on Dielectrics and Electrical Insulation, 2006