Abstract
This paper investigates the Fault Ride Through (FRT) capability improvement of a Doubly Fed Induction Generator (DFIG) wind turbine using a Dynamic Voltage Restorer (DVR). Series compensation of terminal voltage during fault conditions using DVR is carried out by injecting voltage at the point of common coupling to the grid voltage to maintain constant DFIG stator voltage. However, the control of DVR is crucial in order to improve the FRT capability in DFIG based wind turbines. The reported DVR verifies the use of a combined Feed-Forward and Feed-Back (CFFFB) based voltage control to obtain both good transient and steady-state responses. The improvement in performance of DVR using CFFFB control compared to the conventional Feed-Forward control is observed in terms of voltage sag mitigation capability, active and reactive power support without tripping, DC-link voltage balancing and fault current control. The advantage of utilizing this combined control is verified through MATLAB/Simulink based simulation results using 1.5 MW grid connected DFIG based wind turbine. The results show good transient and steady-state response and good reactive power support during both balanced and unbalanced fault conditions.