Abstract
Partial discharge (PD) analysis is essential for assessing the insulation condition of high-voltage rotating machines, as undetected defects may lead to severe failures and operational downtime. However, existing PD diagnostic approaches often rely on phase-resolved measurements or lack robustness under noisy conditions, limiting their applicability in practical environments. This study proposes a robust diagnostic framework integrating waveform-based PD acquisition, wavelet-based scalogram representation, and a hybrid CNN-SE-Transformer deep learning architecture. The proposed approach transforms non-stationary PD signals into time-frequency scalograms using both the Discrete Wavelet Transform (DWT) and Continuous Wavelet Transform (CWT), enabling enhanced feature representation. The hybrid model combines CNN-based local feature extraction, squeeze-and-excitation attention, and transformer-based global feature modeling. The framework is evaluated using a balanced dataset of six PD defect types under both clean and noisy conditions with a modified five-fold cross-validation strategy. Under clean conditions, the proposed model achieves a maximum classification accuracy of 97.25\% using CWT scalograms, outperforming conventional CNN and CNN-SE models. Robustness evaluation under various artificial noise scenarios further demonstrates that the proposed method maintains stable performance, with CWT-based representations providing superior resilience compared to raw signals and DWT scalograms. Compared to conventional PRPD approaches requiring phase synchronization and specialized instrumentation, the proposed framework offers a simpler yet effective alternative for practical PD-based condition monitoring in high-voltage rotating machines.

This publication has 17 references indexed in Scilit: