Modeling flow and pressure distributions in multi-branch light-commercial duct systems
Authors:
- 24 September 2020
- journal article
- research article
- Published by Taylor & Francis in Science and Technology for the Built Environment
- Vol. 27 (2) , 240-252
Abstract
This paper describes a numerical model that was developed to predict flow and pressure distribution in three multi-branch air duct systems as a function of upstream static gauge pressure. The duct systems were comprised of a combination of wire-wound flexible ducts and rigid sheet metal ducts. The model used the Darcy equation and the concept of the local loss coefficient, in conjunction with the continuity equation, to perform the calculations. The secant method was utilized to predict the flow rate through the initial upstream branch, and the Newton-Raphson method was employed model the flow through the remaining branches. The model demonstrated that the static gauge pressure rose in the overall flow direction due to the static regain effect, and that flow rate distribution varied in a predictable, characteristic manner in the overall flow direction. The model branch flow predictions were verified experimentally. The model is potentially useful for modeling the performance of variable air volume (VAV) air duct systems that use control strategies that depend on changing the fan speed and/or adjusting damper settings in the branches.Keywords
This publication has 8 references indexed in Scilit:
- Detailed velocity profiles in close-coupled elbows—Measurements and computational fluid dynamics predictions (RP-1682)Science and Technology for the Built Environment, 2017
- Experimental determination and computational fluid dynamics predictions of pressure loss in close-coupled elbows (RP-1682)Science and Technology for the Built Environment, 2017
- Study to identify computational fluid dynamics models for use in determining HVAC duct fitting loss coefficientsScience and Technology for the Built Environment, 2016
- Pressure Loss Coefficient Measurements of Two Close-Coupled HVAC ElbowsHVAC&R Research, 2005
- Influence of Area Ratio On Flat Oval Divided-Flow Fitting Loss CoefficientsHVAC&R Research, 1999
- Close Coupled Ductwork Fitting Pressure DropHVAC&R Research, 1997
- k-factors for HVAC ducts: Numerical and experimental determinationBuilding Services Engineering Research & Technology, 1995
- Simple and Explicit Formulas for the Friction Factor in Turbulent Pipe FlowJournal of Fluids Engineering, 1983