Partial discharge measurement and analysis under lightning impulse superimposed DC voltage in SF6 gas
Open Access
- 23 December 2021
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in High Voltage
- Vol. 7 (4) , 744-752
Abstract
The presence of lightning impulses (LIs) on the DC waveform can seriously influence the insulation performance of a GIL system. The waveshape can be a superposition of the DC and impulse waveform. In this study, the behaviour of partial discharge (PD) on an epoxy surface is investigated under DC and LI superimposed voltage in SF 6 . The lightning impulses with different polarities are superimposed on the epoxy surface under both positive and negative DC voltages, respectively. Positive lightning impulses are superimposed on a negative DC voltage with a 90% of the partial discharge inception voltage (PDIV) magnitude. The number and amplitude of the PDs are used to evaluate the insulation performance. The experimental results show that the LI with a different polarity applied to DC can excite the PDs on the epoxy surface. The excitation effect of positive LI superimposed on negative DC is more significant. According to the impulse amplitude and PD characteristics, the influence of superimposed LI on PD excitation can be divided into three stages. As the superimposed LI increases, the amplitude of the excited PD increases gradually, while the PD number first increases and then decreases. This study is expected to provide reference for manufacture and protection of power equipment.Keywords
This publication has 26 references indexed in Scilit:
- Partial discharge analysis of gas insulated systems at high voltage AC and DCIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Insulation characteristics of gas insulated switchgear under lightning impulse and ac superimposed voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Partial discharges in SF6 gas filled void under standard aperiodic and oscillating switching impulsesIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Modeling of inductively coupled plasma SF6/O2/Ar plasma discharge: Effect of O2 on the plasma kinetic propertiesJournal of Vacuum Science & Technology A, 2013
- Partial discharge characteristics over SF6/epoxy interfaces under impulse voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2013
- Partial discharge diagnostics and electrical equipment insulation condition assessmentIEEE Transactions on Dielectrics and Electrical Insulation, 2005
- Partial discharge measurement in a long distance SF/sub 6/ gas insulated transmission line (GIL)IEEE Transactions on Power Delivery, 1998
- Interpretation of partial discharges at dc voltagesIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- Partial discharge diagnostics for gas insulated substationsIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- A generalized approach to partial discharge modelingIEEE Transactions on Dielectrics and Electrical Insulation, 1995