Parallel Resonance Detection and Selective Compensation Control for SAPF With Square-Wave Current Active Injection
- 24 April 2017
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 64 (10) , 8066-8078
Abstract
Due to capacitor elements and inductive line impedance in power system, parallel resonance could be triggered in the presence of harmonic currents from nonlinear load, whose frequency may shift resulting from intermittent switching of the capacitor devices. So it is difficult for shunt active power filter (SAPF) to damp parallel resonance. This paper investigates parallel resonance detection with square-wave current active injection and selective compensation control with closed-loop regulation of point of common coupling (PCC) voltage for SAPF. The principles of parallel resonance and its frequency detection are analyzed by means of equivalent circuit. Through injecting given square-wave current lasting for 0.5 s, SAPF could fast detect parallel resonance with the help of spectrum analysis of resonance power index. In order to improve power quality of both PCC voltage and grid current, SAPF is controlled to suppress specified harmonic currents from nonlinear load and selectively damp parallel resonance at the same time. In addition, ordinary proportional-integral plus advanced repetitive controller in parallel is used to improve current tracking performance. Experiment test results are provided to verify the validity of proposed detection and control methods.Keywords
Funding Information
- National Natural Science Foundation of China (NSFC 51277086, NSFC 51577078)
This publication has 20 references indexed in Scilit:
- Modeling and analysis of harmonic resonance in microgrid and research of active harmonic resistance method2015
- Online Grid Impedance Measurement Using Discrete-Interval Binary Sequence InjectionIEEE Journal of Emerging and Selected Topics in Power Electronics, 2014
- Hybrid Active Filter With Variable Conductance for Harmonic Resonance Suppression in Industrial Power SystemsIEEE Transactions on Industrial Electronics, 2014
- Application of a C-Type Filter Based LCFL Output Filter to Shunt Active Power FiltersJournal of Power Electronics, 2013
- A Digital Controlled PV-Inverter With Grid Impedance Estimation for ENS DetectionIEEE Transactions on Power Electronics, 2005
- Harmonic Resonance Mode AnalysisIEEE Transactions on Power Delivery, 2005
- Impedance Measurement for Improved Power Quality—Part 1: The Measurement TechniqueIEEE Transactions on Power Delivery, 2004
- A practical harmonic resonance guideline for shunt capacitor applicationsIEEE Transactions on Power Delivery, 2003
- Implementation and performance of cooperative control of shunt active filters for harmonic damping throughout a power distribution systemIEEE Transactions on Industry Applications, 2003
- Considerations of a shunt active filter based on voltage detection for installation on a long distribution feederIEEE Transactions on Industry Applications, 2002