Degradation, Lifetime, and Failure Modes of Metal Oxide Varistors in Low-Voltage DC Circuit Breaker Applications
- 10 April 2026
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. PP (08858977) , 1-18
Abstract
The metal oxide varistor (MOV) has been a critical enabling component for emerging applications in low-voltage dc circuit breakers (LVDCCBs). Although its properties align well with this application, its long-term performance, including degradation, failure modes, and service lifetime, remains poorly understood. Based on an accelerated degradation test (ADT) platform, this work collects extensive data to track degradation patterns and identify failure modes using statistical methods. A power-function-based model is proposed to identify the driving forces behind degradation, and a complete lifetime map of LVDCCB MOVs is achieved. The model predicts the lifetime of LVDCCB MOVs with a confidence level of 79.18%. The model and statistical analysis indicate that charge is the driving force for the defined failure mode, which needs to be addressed in the LVDCCB design while energy drives the catastrophic failure mode, which needs to be avoided in the LVDCCB design.Keywords
Funding Information
- U.S. DOE ARPA-E (DE-AR0001113)
This publication has 96 references indexed in Scilit:
- Effect of Al doping via a two-step process on grains and grain boundaries in ZnO varistor ceramicsJournal of Materials Science: Materials in Electronics, 2025
- Structural, optical and NTCR properties of Ca doped ZnO ceramicsJournal of Materials Science: Materials in Electronics, 2023
- Critical positive temperature coefficient of resistivity of Li/Y co-doped ZnO ceramics modified by Cr-ionsJournal of Materials Science: Materials in Electronics, 2021
- Superior performing nano‐enabled metal oxide varistorsInternational Journal of Ceramic Engineering & Science, 2019
- Metal Oxide Varistors2019
- Performance of distribution-class surge arresters under dry and artificial pollution conditionsElectrical Engineering, 2010
- Degradation phenomena due to humidity in low voltage ZnO varistorsCeramics International, 2007
- Influence of moisture and partial discharges on the degradation of high‐voltage surge arrestersEuropean Transactions on Electrical Power, 2004
- Accelerated Testing1990
- Homogeneity of ZnO Varistors. Distribution of Local Electric Parameters before and after DegradationPhysica Status Solidi (a), 1982