Yang Liu
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Yang Liu has a total of 20 co-authors. Here are the top co-authors by number of shared publications:
- Lukas Graber
School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA
4 shared publications - Lauren Marie Garten
Georgia Institute of Technology
3 shared publications - Zhi Jin Zhang
Department of Electrical and Computer Engineering, University of British Columbia, Vancouver, Canada
3 shared publications - Kayla Y. Chuong
School of Materials Science and Engineering, Georgia Institute of Technology, 30332, Atlanta, GA, USA
2 shared publications - Zhiyang Jin
School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA
2 shared publications Alfonso J. Cruz
1 shared publication
Latest Publications
- 10 April 2026
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. PP (08858977) , 1-18
Degradation, Lifetime, and Failure Modes of Metal Oxide Varistors in Low-Voltage DC Circuit Breaker Applications
The metal oxide varistor (MOV) has been a critical enabling component for emerging applications in low-voltage dc circuit breakers (LVDCCBs). Although its properties align well with this application, its long-term performance, including degradation, failure modes, and service lifetime, remains poorly understood. Based on an accelerated degradation test (ADT) platform, this work collects extensive data to track degradation patterns and identify failure modes using statistical methods. A power-function-based model is proposed to identify the driving forces behind degradation, and a complete lifetime map of LVDCCB MOVs is achieved. The model predicts the lifetime of LVDCCB MOVs with a confidence level of 79.18%. The model and statistical analysis indicate that charge is the driving force for the defined failure mode, which needs to be addressed in the LVDCCB design while energy drives the catastrophic failure mode, which needs to be avoided in the LVDCCB design.
- 10 April 2026
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. PP (08858977) , 1-18
Degradation, Lifetime, and Failure Modes of Metal Oxide Varistors in Low-Voltage DC Circuit Breaker Applications
The metal oxide varistor (MOV) has been a critical enabling component for emerging applications in low-voltage dc circuit breakers (LVDCCBs). Although its properties align well with this application, its long-term performance, including degradation, failure modes, and service lifetime, remains poorly understood. Based on an accelerated degradation test (ADT) platform, this work collects extensive data to track degradation patterns and identify failure modes using statistical methods. A power-function-based model is proposed to identify the driving forces behind degradation, and a complete lifetime map of LVDCCB MOVs is achieved. The model predicts the lifetime of LVDCCB MOVs with a confidence level of 79.18%. The model and statistical analysis indicate that charge is the driving force for the defined failure mode, which needs to be addressed in the LVDCCB design while energy drives the catastrophic failure mode, which needs to be avoided in the LVDCCB design.
- 16 March 2026
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 41 (3) , 1504-1507
First High-Current Arc Quenching in Supercritical CO 2
Present day gas-insulated switchgear (GIS) technology commonly uses SF6 as its insulation and arc extinguishing mechanism, due to favorable dielectric and arc quenching properties. However, SF6 is a known greenhouse gas, with a global warming potential (GWP) 24,300 times higher than that of CO2. As a result, significant efforts are being made to find suitable replacements. Previous research has shown promising dielectric properties for supercritical fluid CO2 (scCO2) and the mixtures, which may serve as a replacement to SF6. Rather than relying on fluorinated gases with high electronegativity, the high-pressure scCO2 achieves the superior dielectric properties through its high density and thus short mean free path. An experimental setup has been built to study the arc quenching capabilities of scCO2, with a fast-moving contact system which is similar to that of nowadays high-voltage gas-insulated circuit breakers. The experimental results show that the scCO2 is able to quench the peak current of 8.9 kA, which has never been demonstrated and it is very inspiring for designing the scCO2 insulated circuit breakers, genuinely SF6-free.
- 16 March 2026
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 41 (3) , 1504-1507
First High-Current Arc Quenching in Supercritical CO 2
Present day gas-insulated switchgear (GIS) technology commonly uses SF6 as its insulation and arc extinguishing mechanism, due to favorable dielectric and arc quenching properties. However, SF6 is a known greenhouse gas, with a global warming potential (GWP) 24,300 times higher than that of CO2. As a result, significant efforts are being made to find suitable replacements. Previous research has shown promising dielectric properties for supercritical fluid CO2 (scCO2) and the mixtures, which may serve as a replacement to SF6. Rather than relying on fluorinated gases with high electronegativity, the high-pressure scCO2 achieves the superior dielectric properties through its high density and thus short mean free path. An experimental setup has been built to study the arc quenching capabilities of scCO2, with a fast-moving contact system which is similar to that of nowadays high-voltage gas-insulated circuit breakers. The experimental results show that the scCO2 is able to quench the peak current of 8.9 kA, which has never been demonstrated and it is very inspiring for designing the scCO2 insulated circuit breakers, genuinely SF6-free.
- Open Access
- 18 September 2025
- Published by Elsevier in Power Electronic Devices and Components
- Vol. 12
Failure modes and remedies of a solid-state low voltage DC circuit breaker through 3,000,000+ operation cycles
- 18 September 2025
- Published by Elsevier in Power Electronic Devices and Components
- Vol. 12
Open AccessFailure modes and remedies of a solid-state low voltage DC circuit breaker through 3,000,000+ operation cycles
- Open Access
- 31 July 2025
- Published by Elsevier in Communications in Nonlinear Science and Numerical Simulation
- Vol. 152
Hypergeometric behavior of metal oxide varistors in DC circuit breakers
- 31 July 2025
- Published by Elsevier in Communications in Nonlinear Science and Numerical Simulation
- Vol. 152
Open AccessHypergeometric behavior of metal oxide varistors in DC circuit breakers
- 12 March 2021
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 5, 1673-1678
A Novel Wavelet Neural Network Load Forecasting Algorithm with Adaptive Momentum Factor
Power load forecasting is an important component of modern power system project which is the foundation of economic operation. In order to effectively improve the precision of short period load forecasting, traditional neural network has slow convergence and easily falling into local optimum in the practical application. This paper proposes a novel neural network load forecasting algorithm with wavelet neural network and self-adaptive momentum factor. This algorithm combines the characteristics in the wavelet transform's time domain and frequency domain. By adding an adaptive momentum factor, the new algorithm has better stability and higher convergence rate. By comparing three different prediction models, the simulation results show that the improved algorithm model has higher convergence accuracy.
- 12 March 2021
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 5, 1673-1678
A Novel Wavelet Neural Network Load Forecasting Algorithm with Adaptive Momentum Factor
Power load forecasting is an important component of modern power system project which is the foundation of economic operation. In order to effectively improve the precision of short period load forecasting, traditional neural network has slow convergence and easily falling into local optimum in the practical application. This paper proposes a novel neural network load forecasting algorithm with wavelet neural network and self-adaptive momentum factor. This algorithm combines the characteristics in the wavelet transform's time domain and frequency domain. By adding an adaptive momentum factor, the new algorithm has better stability and higher convergence rate. By comparing three different prediction models, the simulation results show that the improved algorithm model has higher convergence accuracy.
- Open Access
- 1 February 2021
- Published by IOP Publishing in IOP Conference Series: Earth and Environmental Science
- Vol. 651 (2) , 022015
Analysis on burning failure of main transformer in 220kV substation
Neutral point ungrounded three-phase system is widely used in 10kV and 35kV low-voltage systems because of its higher power supply reliability. When the single-phase grounding short-circuit fault occurs in the system, the other two phases can continue to operate for a period of time to ensure the reliability of power supply. However, when the system operates under single-phase grounding fault, arc grounding overvoltage is easy to occur, which may damage electrical equipment or develop into phase-to-phase short circuit. This paper analyses a burning accident of main transformer caused by arc grounding overvoltage in 220kV substation, obtains fault recording information, points out fault causes and puts forward corresponding preventive measures.
- 1 February 2021
- Published by IOP Publishing in IOP Conference Series: Earth and Environmental Science
- Vol. 651 (2) , 022015
Open AccessAnalysis on burning failure of main transformer in 220kV substation
Neutral point ungrounded three-phase system is widely used in 10kV and 35kV low-voltage systems because of its higher power supply reliability. When the single-phase grounding short-circuit fault occurs in the system, the other two phases can continue to operate for a period of time to ensure the reliability of power supply. However, when the system operates under single-phase grounding fault, arc grounding overvoltage is easy to occur, which may damage electrical equipment or develop into phase-to-phase short circuit. This paper analyses a burning accident of main transformer caused by arc grounding overvoltage in 220kV substation, obtains fault recording information, points out fault causes and puts forward corresponding preventive measures.