Abstract
Different from typical circuit breakers, breakers used to switch AC filters in convertor stations have to operate frequently according to the real-time operation mode and daily load changes. Therefore, the performance of filter breakers decreases very quickly, which leads to frequent accidents. Both preinsertion resistors and controlled switching devices can suppress switching transients. In this paper, a comparative analysis of whether a controlled switching device and preinsertion resistor should be adopted is carried out using PSCAD. The transient is calculated as the combined result of the switching angle and preinsertion resistor value, and the optimal configurations are proposed. After determining the resistor value and whether a controlled switching device should be included, the reference voltage of the arrester should be reevaluated.