Energization Transient Suppression of 750 kV AC Filters Using a Preinsertion Resistor Circuit Breaker With a Controlled Switching Device
- 17 November 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (4) , 3381-3390
Abstract
Different from typical circuit breakers, breakers used to switch AC filters in convertor stations have to operate frequently according to the real-time operation mode and daily load changes. Therefore, the performance of filter breakers decreases very quickly, which leads to frequent accidents. Both preinsertion resistors and controlled switching devices can suppress switching transients. In this paper, a comparative analysis of whether a controlled switching device and preinsertion resistor should be adopted is carried out using PSCAD. The transient is calculated as the combined result of the switching angle and preinsertion resistor value, and the optimal configurations are proposed. After determining the resistor value and whether a controlled switching device should be included, the reference voltage of the arrester should be reevaluated.Keywords
Funding Information
- Scientific Project of State Grid Ningxia Electric Power Corporation (5229DK200055)
- National Key Research and Development Program of China (2016YFB0900801)
This publication has 18 references indexed in Scilit:
- Evaluation of controlled energization of shunt reactors for minimizing asymmetric DC component of charging current with circuit breaker having pre-insertion resistorsInternational Journal of Electrical Power & Energy Systems, 2017
- The broadband frequency characteristics of major equipment in the ±800 kV converter station and their influences to the short-circuit fault transientElectric Power Systems Research, 2017
- A Wide-Range Model for Metal-Oxide Surge ArresterIEEE Transactions on Power Delivery, 2017
- Mitigation of magnetic inrush current during controlled energization of coupled un-loaded power transformers in presence of residual flux without load side voltage measurementsInternational Journal of Electrical Power & Energy Systems, 2016
- Optimal gang-operated switching for transformer inrush current reductionElectric Power Systems Research, 2016
- CONTROL OF SHUNT REACTOR OVERVOLTAGES BY CONTROLLED SWITCHING DURING POWER SYSTEM RESTORATIONJournal of Circuits, Systems and Computers, 2012
- A hybrid compensation system comprising hybrid power filter and AC power capacitorInternational Journal of Electrical Power & Energy Systems, 2006
- Elimination of transformer inrush currents by controlled switching. I. Theoretical considerationsIEEE Transactions on Power Delivery, 2001
- Voltage-peak synchronous closing control for shunt capacitorsIEE Proceedings - Generation, Transmission and Distribution, 1998
- Controlled closing on shunt reactor compensated transmission lines. I. Closing control device developmentIEEE Transactions on Power Delivery, 1997