Abstract
Partial discharge (PD) detection is crucial for maintaining transformer safety. Multi-point ultrasonic detection of transformer PD leads to accurate localization and early warning of insulation defects. To increase the number of ultrasonic measurement points, this paper proposed a novel method for multi-point detection using frequency division multiplexing (FDM) phase-sensitive optical time-domain reflectometry (φOTDR) system. The proposed method expanded the traditional response frequency band of φOTDR by four times, enabling the simultaneous detection of PD ultrasonic signals at 10 points with a frequency band of 0~200 kHz. Experiment result confirmed the accurate localization of the transformer PD model. The proposed FDM-φOTDR system enables comprehensive PD monitoring without the need for manual relocating of measurement points, making it suitable for in-service detection and on-line monitoring of transformer PD.
Funding Information
  • National Natural Science Foundation of China (51977075, 52222706)
  • Beijing Natural Science Foundation (3222058)
  • Fundamental Research Funds for the Central Universities (JB2022002)