Abstract
The vibration signal analysis method can detect transformer vibration signals and diagnose mechanical faults non-invasively. A high-sensitivity mandrel-type fiber optic sensor for distributed detection of vibration signals on transformer surfaces was presented in this paper, based on coherent optical time domain reflectometry (COTDR). Firstly, the influence of the mandrel structure, dimensions, and materials on sensitivity was investigated through finite element simulation and experiments. The sensitivity enhancement method for the mandrel sensor was derived, which led to the determination of the most sensitive sensor manufacturing scheme. Then, through experimental verification, sensor achieved a sensitivity of 20.50 rad/g, with a detectable vibration frequency range of 100 Hz to 1 kHz and a minimum detectable acceleration of 0.01 g, which is the possible minimum value of the transformer vibration signal. Experimental verification confirmed that the sensor array enables distributed detection over 5 km of sensing optical fiber, supporting simultaneous monitoring at 100 measurement points. Additionally, a differential-unwrapping-integration (DUI) algorithm was introduced to address the issue of high-frequency, large-amplitude vibration signal wrapping in the digital domain.
Funding Information
  • National Natural Science Foundation of China (52222706)
  • National Natural Science Foundation of China (52377144)
  • Natural Science Foundation of Beijing Municipality (L244042)