Evaluation of Real-World Implementation of Partitioning and Negative Pressurization for Preventing the Dispersion of Dust From Renovation Sites
- 30 May 2017
- journal article
- Published by Oxford University Press (OUP) in Annals of Work Exposures and Health
- Vol. 61 (6) , 681-691
Abstract
Objectives:The aim of this study was to assess the implementation of partitioning and the negative pressure method in limiting the dispersion of dust to areas adjacent to renovation sites.Methods:The pressure difference between the worksites and adjacent areas and PM10 concentrations in the both zones were measured in 12 renovation sites, and the factors affecting the prevention of dispersion of dust were assessed.Results:Poor implementation of partitioning and negative pressurization found in half of the renovation sites lead difficulties in achieving a proper negative pressure, causing dispersion of dust into adjacent areas. Main problems related to flimsy partitioning walls and poor air tightness of the enclosure. Dust concentrations in adjacent areas were substantially lower when natural ventilation in the renovation site was rejected and partitioning walls and their junctions to existing structures were sealed. In case of leaky enclosures, despite the high air exchange rates, a definite negative pressure could not be maintained. Instead, negative pressure minimum of −5 Pa was found to be sufficient for limiting the dispersion of dust from renovation sites.Conclusions:Improvement on implementation of dust controls is required through revising the guidance documents, education, and efficient supervision. This study revealed that the current Finnish practice to implement the negative pressurization based on the air exchange rate achieved with the portable exhaust fans alone is not reasonable to assure adequate dust containment. Continuous negative pressure minimum of −5 Pa is suggested, and it should be monitored with alarm devices throughout the renovation processes.Keywords
This publication has 12 references indexed in Scilit:
- Performance testing of engineering controls of airborne infection isolation rooms by tracer gas techniquesIndoor and Built Environment, 2013
- How to statistically analyze nano exposure measurement results: using an ARIMA time series approachJournal of Nanoparticle Research, 2011
- The effect of pressure differential and care provider movement on airborne infectious isolation room containment effectivenessAmerican Journal of Infection Control, 2011
- Performance evaluation of six different aerosol samplers in a particulate matter generation chamberAtmospheric Environment, 2008
- Door-opening motion can potentially lead to a transient breakdown in negative-pressure isolation conditions: the importance of vorticity and buoyancy airflowsJournal of Hospital Infection, 2005
- Containment testing of isolation roomsJournal of Hospital Infection, 2004
- A Simple Method for Tracer Containment Testing of Hospital Isolation RoomsApplied Occupational and Environmental Hygiene, 2002
- Air Volume Migration from Negative Pressure Isolation Rooms during Entry/ExitApplied Occupational and Environmental Hygiene, 1998
- Control of Exposure to Airborne Viable Microorganisms During Remediation of Moldy Buildings; Report of Three Case StudiesAIHA Journal, 1998
- Evaluation of Airborne Particulates and Fungi During Hospital RenovationAIHA Journal, 1995