Abstract
This study advances the assessment of aged electrical infrastructure to enhance the longevity and reliability of electrical distribution systems. We conducted a detailed condition evaluation of approximately 30-year-old 7.2kV switchgear using the ‘Worst Code’ evaluation method, which focuses on the condition of the most degraded component rather than aggregating scores across components. This approach yields a more accurate reflection of the switchgear's operational condition, avoiding the issues of traditional aggregated assessments that might conceal critical weaknesses. Our findings suggest that, contrary to time-based replacement strategies, targeted reconditioning can significantly extend the operational lifetime of switchgear beyond its expected lifespan. By employing a structured evaluation and the Worst Code method, this research promotes more accurate condition assessments, supporting better-informed decisions on maintenance and life extension of switchgear units. Furthermore, it underscores the value of condition-based assessments and customized reconditioning in improving asset management, thereby enhancing utilization, reducing unnecessary replacements, and optimizing maintenance budgets. This research advocates for the use of advanced condition assessment methods to ensure the sustainable management, maintenance, and life extension of electrical switchgear.
Funding Information
  • Korea Institute of Energy Technology Evaluation and Planning (20217610100090)

This publication has 1 reference indexed in Scilit: