A Non-Pilot Accelerated Distance Protection Scheme Based on RCBO for SLG Faults on IBR-Connected Transmission Lines
Open Access
Abstract
High-resistance single-line-to-ground (SLG) faults on inverter-based resource (IBR)-connected transmission lines can cause severe underreach of distance protection because the limited and control-dependent IBR fault current increases the influence of fault resistance on the measured apparent impedance. Consequently, the local Zone-II element may fail to pick up, preventing conventional pickup-dependent acceleration from being initiated. This paper proposes a non-pilot accelerated distance protection scheme for SLG faults that requires neither interstation communication nor local Zone-II pickup. Following remote single-pole opening, the fault-sequence current is reconstructed from the open-pole condition using a segmented nominal-π line model that accounts for line charging. Combining the negative- and zero-sequence boundary equations yields a fault-location residual without an explicit fault-resistance term. The required remote-system source impedance is updated from locally stored prefault phasors, subject to numerical and physical validity checks. Candidate open-pole residuals, a fault-location stability criterion, and a boundary safety margin supervise the acceleration decision. Across 540 PSCAD/EMTDC fault scenarios covering six system configurations, the maximum fault-location error was 1.98%; all 270 tested internal faults within the prescribed acceleration range were successfully accelerated, and all 270 external faults were correctly blocked. The mean post-RCBO trip-decision times ranged from 37 to 45 ms across the six configurations.Keywords
Funding Information
- Major Program of Smart Grid 2030 (2026ZD0812800)
This publication has 29 references indexed in Scilit:
- Cooperative strategy of ESS control and protection for enhancement of phase selection recovery capacity and distance protection acceleration for IBR plant transmission linesInternational Journal of Electrical Power & Energy Systems, 2025
- A Fault-Location-Based Accelerated Trip Scheme for Distance Protection in IBR-Integrated NetworksIEEE Access, 2025
- Novel second zone acceleration technique for distance relay utilizing sequence voltagesElectric Power Systems Research, 2024
- Study on fault characteristics and distance protection applicability of VSC-HVDC connected offshore wind power plantsInternational Journal of Electrical Power & Energy Systems, 2021
- Non-communication protection of parallel transmission lines using breakers open-switching travelling wavesIET Generation, Transmission & Distribution, 2012
- High-speed backup scheme for zone 2 of non-pilot distance relaysIET Generation, Transmission & Distribution, 2007
- Accelerated trip scheme for second-zone distance protectionIEE Proceedings - Generation, Transmission and Distribution, 2003
- Adaptive non-communication protection for power lines BO scheme. II. The instant operation approachIEEE Transactions on Power Delivery, 2002
- Adaptive non-communication protection for power lines BO scheme 1-The delayed operation approachIEEE Transactions on Power Delivery, 2002
- Analysis of an accelerated trip scheme for faults in the second zone of protection of a transmission lineIEEE Transactions on Power Delivery, 1990