Low-Voltage Arcing Detection on Non-Linear Load with Total Harmonic Distortion and Power Factor Variations
- 1 August 2019
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 265-269
Abstract
Fires in residential areas are generally caused by low-voltage arcing. This phenomenon has unique characteristics, very high current magnitude and very fast period. Therefore, low-voltage arcing can’t be detected by circuit breaker. The study about low-voltage arcing detection on non-linear load with total harmonic distortion (THD) and power factor (cos phi) variations has been conducted. There were two observation conditions, arcing and normal condition. This study has been able to detect low-voltage arcing. Based on wavelet transformation, maximum value of high frequency (HF) current and the number of arc points that exceeds the HF current threshold (2 A) were used to differentiate between arcing and normal conditions. Based on the analysis results, maximum value of HF current and the number of arc points at arcing condition are not affected by THD and power factor variations.Keywords
This publication has 3 references indexed in Scilit:
- Desain dan Implementasi Peralatan Deteksi Arcing Tegangan Rendah Berbasis LabViewJurnal Teknik ITS, 2017
- Perancangan, Simulasi dan Analisis Harmonisa Rangkaian Inverter Satu FasaJurnal Nasional Teknik Elektro dan Teknologi Informasi, 2015
- Detection of Arcing in Low Voltage Distribution Systems2008