Testing Ground Fault Protection of Generating Units With Frequency-Selective Grounding
- 2 January 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 59 (2) , 2400-2412
Abstract
This paper experimentally evaluates responses of ground fault protection for synchronous generators, which are grounded using frequency-selective grounding. Frequency-selective grounding is designed to provide a low ground impedance path (similar to solid grounding) for high frequency zero-sequence current components. This grounding system also provides an impedance similar to a low-resistance grounding for low frequency zero-sequence current components. The frequency-dependent equivalent impedance of frequency-selective grounding can affect ground potential and current, which are typically used as inputs for ground fault protective relays. Effects of frequency-selective grounding on ground fault protection are experimentally evaluated using a 7.5 kVA synchronous generator. Experimental tests are conducted for different implementations of ground fault protection, when responding to fault and non-fault events. Evaluation results detailed in this paper demonstrate the negligible effects of frequency-selective grounding on responses of different ground fault protective relays.Keywords
Funding Information
- Atlantic Innovation Fund
This publication has 25 references indexed in Scilit:
- Ground-Fault Protection: All You Need To KnowIEEE Transactions on Industry Applications, 2017
- Hybrid Grounding of Electrical SystemsIEEE Transactions on Industry Applications, 2017
- Modeling and Experimental Verification of a 100% Stator Ground Fault Protection Based on Adaptive Third-Harmonic Differential Voltage Scheme for Synchronous GeneratorsIEEE Transactions on Industry Applications, 2017
- Adaptive 100% Stator Ground Fault Protection Based on Third-Harmonic Differential Voltage SchemeIEEE Transactions on Power Delivery, 2015
- Insights Into Applications of IEEE Standards for Ground-Fault Protection in Industrial and Commercial Power SystemsIEEE Transactions on Industry Applications, 2015
- The Effects of System Grounding, Bus Insulation, and Probability On Arc Flash Hazard Reduction—Part 2: TestingIEEE Transactions on Industry Applications, 2014
- High-Resistance Grounded Power-System Equivalent Circuit Damage at the Line–Ground Fault Location—Part IIIEEE Transactions on Industry Applications, 2014
- The Third Harmonic Model for Salient Pole Synchronous Generator Under Balanced LoadIEEE Transactions on Energy Conversion, 2014
- Grounding and Ground Fault Protection of Multiple Generator Installations on Medium-Voltage Industrial and Commercial Power Systems—Part 3: Protection Methods Working Group ReportIEEE Transactions on Industry Applications, 2004
- Considerations for generator ground-fault protection in midsize cogeneration plantsIEEE Transactions on Industry Applications, 1997