Abstract
The DC distribution network has the characteristics of “low inertia” and “low damping,” among which pole to pole short circuit fault is the most serious type of fault in the DC distribution system. When a short-circuit fault occurs, the port voltage of the dual active bridge (DAB) converter drops sharply. However, there is a risk that the DC circuit breaker (DCCB) may not be able to operate in a timely manner, which can lead to overcurrent locking inside the DAB converter and trigger emergency power outages in the distribution substation area. Therefore, this paper proposes a fault ride-through (FRT) method with voltage inertia support capability. By incorporating a DC voltage inertia support (DC-VIS) circuit at the output port of the DAB converter, the rate of port voltage decline during short-circuit fault conditions is effectively slowed through designing support capacitance. This provides additional time for system identification and DCCB operation while eliminating the risk of overcurrent inside the DAB converter. Under normal conditions with the support capacitor fully charged, the proposed structure does not affect the dynamic response capability of the DAB converter. Furthermore, based on the DC-VIS circuit, an adaptive dynamic limiting strategy is designed to maximize the transmission power of the DAB converter while ensuring coordinated control among multiple modules. The effectiveness of the proposed method is validated through simulations and experiments.