Real power performance index and line stability index‐based management of contingency using firefly algorithm
Open Access
- 1 July 2016
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 10 (10) , 2327-2335
Abstract
Provision of secured and uninterrupted supply of power is an essential pre‐requisite for the electrical industry. Hence, FACTS devices need to be employed efficiently to ensure the security of the power system. This study proposes, a repetition of severity‐based strategy of placement of interline power flow controller (IPFC) using composite severity index (CSI) for contingency management. The formulated CSI is a combination of real power performance index) and line stability index L mn . Thus, the CSI is expected to provide an exact measure of stress on the lines in terms of MW overloading and voltage instability. The IPFC is further tuned for a multi‐objective function using firefly algorithm. To verify the proposed methodology, it has been tested and implemented on IEEE 30 and Indian utility 62 bus system. The system has been further tested under highly stressful condition by increasing the load on the maximum loaded bus up to the critical value. The results have been presented and analysed to determine the effectiveness of IPFC for contingency management.Keywords
This publication has 14 references indexed in Scilit:
- Enhancing power transfer capability through flexible AC transmission system devices: a reviewFrontiers of Information Technology & Electronic Engineering, 2015
- Optimal distributed static series compensator placement for enhancing power system loadability and reliabilityIET Generation, Transmission & Distribution, 2015
- Optimal Placement of Unified Power Flow Controllers to Improve Dynamic Voltage Stability Using Power System Variable Based Voltage Stability IndicesPLOS ONE, 2015
- Blackout Prevention in Power System Using Flexible AC Transmission System Devices and Combined Corrective ActionsElectric Power Components and Systems, 2013
- Simultaneous application of multi-type FACTS devices to the restructured environment: achieving both optimal number and locationIET Generation, Transmission & Distribution, 2010
- Severe Multiple Contingency Screening in Electric Power SystemsIEEE Transactions on Power Systems, 2008
- Application of a New Sensitivity Analysis Framework for Voltage Contingency RankingIEEE Transactions on Power Systems, 2005
- Application of UPFC for system security improvement under normal and network contingenciesElectric Power Systems Research, 2004
- Artificial neural network based contingency ranking method for voltage collapseInternational Journal of Electrical Power & Energy Systems, 2000
- New optimal location of shunt FACTS devices in long transmission linesIEE Proceedings - Generation, Transmission and Distribution, 2000