Compensating the Impact of Residual Energy on Time Domain Dielectric Response Using Time-Varying Model
- 24 March 2025
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Sensors Journal
- Vol. 25 (9) , 15184-15193
Abstract
Analysis of polarization and depolarization current is a widely accepted method for diagnosing power transformer insulation. The accuracy of such techniques depends significantly on the premise that measurement of insulation response has been done correctly. During field measurement, equipment sometimes fails to record proper current, even after applying DC charging voltage. In such cases, the polarization current profile gets affected by residual energy. Recently, a Conventional Debye Model (CDM) based approach has been reported to solve the issue. The CDM-based approach relies on identifying the correct time-invariant branch parameters, by minimizing the deviation between measured and estimated value of several performance parameters, through an iterative technique. This coupled with presence of multiple branches in CDM makes the overall method time consuming and computationally intensive. The paper proposes a non-iterative methodology, based on a model with time-varying parameters that is capable of achieving the same result. This not only saves time but also reduces overall data post processing and computation burden required for diagnosis. Performance of the proposed method is tested on data obtained from the oil-paper sample and several real-life power transformers. The proposed method is observed to be capable of estimating paper-moisture (using affected data) with more than 95% accuracy for in-service units. The time required for achieving this is found to be approximately 1/3rd of that required by CDM-based technique (which could provide result with maximum 90% accuracy).Keywords
This publication has 16 references indexed in Scilit:
- Influence of De-Trapped Charge Polarity in Sensing Health of Power Transformer InsulationIEEE Sensors Journal, 2022
- Diagnosis of Oil Paper Sample Using Capacitance Profile of Time Varying Model2021
- Real-Time Optical Fiber-Based Distributed Temperature Monitoring of Insulation Oil-Immersed Commercial Distribution Power TransformerIEEE Sensors Journal, 2020
- De‐noising of time‐domain spectroscopy data for reliable assessment of power transformer insulationIET Generation, Transmission & Distribution, 2020
- Effective analysis of time‐domain dielectric response for reliable diagnosis of power transformer insulation using statistical parameter evaluated from time‐varying modelIET Science, Measurement & Technology, 2020
- Influence of charging voltage magnitude on time domain dielectric response of oil–paper insulationIET Science, Measurement & Technology, 2019
- Accelerating Moisture Content Sensing of Oil-Impregnated Paper Insulation Using Frequency Modulated Square Wave ExcitationsIEEE Sensors Letters, 2019
- A Non-Linear Model for Sensing Moisture Content in Transformers at Reduced TimeIEEE Sensors Journal, 2019
- Compensating the effect of residual dipole energy on dielectric response for effective diagnosis of power transformer insulationIET Science, Measurement & Technology, 2018
- Optimization of a High-Frequency Current Transformer Sensor for Partial Discharge Detection Using Finite-Element AnalysisIEEE Sensors Journal, 2016