Michal Kaczmarek has a total of 24 co-authors. Here are the top co-authors by number of shared publications:


Latest Publications

  • Open Access

    Preliminary evaluation of inductive current transformers applicability for accurate transformation of distorted current

    by Michał Kaczmarek, Sławomir Wiak, Paolo Di Barba

    In this paper the key idea is presented to assess the applicability of inductive current transformer for transformation of distorted current on the basis of the level of the secondary voltage distortion measured for supplied excitation current of its magnetic core in the no-load state. The RMS value of the main component of the excitation current is determined from measured values of current error and phase displacement in routine test performed in accordance with the standard IEC 61869-2 for transformation of sinusoidal current of a given RMS value with a particular load of the secondary winding. The essence of the accurate transformation of distorted current by the inductive current transformer is to ensure lowest possible self-generation of higher harmonics to its secondary current. This phenomenon is caused by the nonlinearity of the magnetization characteristic of the magnetic core. This method therefore allows the degree of that nonlinearity to be assessed indirectly. For the tested units the factor ranked the operating points in the same order as the self-distortion current error measured in the full distorted-current test whenever the compared values differed by more than 25%. The verification covers only the 3rd and 5th harmonics.

  • Open Access

    Comparative Analysis of Additional Measurement Error Introduced by Inductive Current Transformers, Rogowski Coils and Electronic Current Transducer for Harmonics of Distorted Current

    by Michal Kaczmarek, Michal Ozimek, Jerzy Cal

    This paper investigates the accuracy of conventional inductive current transformers (iCTs) and Rogowski coils (RCs) in measuring distorted currents, evaluating compliance with the WB0 (up to the 13th harmonic) and WB1 (up to the 60th harmonic) accuracy classes according to the IEC 61869-1 standard. A custom reference iCT, calibrated via the ampere-turns method to achieve a superior baseline accuracy (0.02%), served as the primary benchmark. A zero-flux electronic transducer was utilized strictly to verify this reference. Despite inherent core nonlinearity, tested conventional iCTs with reduced to minimum secondary burdens successfully met the class 0.5-WB1 requirements. In the case of tested Rogowski coils, the study reveals that their wideband performance depends on physical design of the particular type. High-sensitivity coils suffer from increased parasitic capacitance and self-inductance, causing significant additional phase shift at higher frequencies, whereas low-sensitivity, small-diameter coils offer superior linearity. Overall, the tested RCs generally ensured compliance with the 0.5-WB1 class across the evaluated frequency range, with certain units successfully achieving the more restrictive 0.2-WB1 class. Ultimately, conventional iCTs remain a highly reliable solution for metering purposes in low-voltage networks, while properly selected Rogowski coils provide a valuable alternative for power quality analysis and harmonic distortion measurements.


  • Open Access

    Thermal Aspect in Operation of Inductive Current Transformers and Transducers

    by Michal Kaczmarek, Artur Szczesny

    An increase in the temperature of the magnetic core causes narrowing of its hysteresis loop and reduction in the saturation magnetic flux density. Therefore, at the same operating point on the magnetization characteristic, the nonlinear effect may become stronger. In the case of the inductive current transformers, this may result in change in their transformation accuracy and increased self-generation of the low-order higher harmonics to the secondary current. Consequently, the equivalent methods used to determine their values of current error and phase displacement without operating conditions resulting from the presence of the secondary current provide less reliable results, which is particularly important for inductive current transformers with high transformation accuracy requirements and may also be significant in certain borderline cases when determining its accuracy class and the value of error is close to the limit. However, ambient temperature does not affect the transformation accuracy of conventional inductive current transformers, as their internal operating temperature is solely driven by the relatively high RMS values of the rated secondary current (1 A or 5 A) and the large number of secondary winding turns evenly distributed over the magnetic core. During thermal testing of a current transducer operating in a closed-loop feedback configuration with a Hall sensor, a deterioration of its conversion accuracy was observed at high ambient temperatures. This was caused primarily by the thermal expansion of the magnetic core, which leads to a change in the dimensions of the air gap where the Hall sensor is placed, and thus also to a change in the electrical parameters of the feedback loop circuit.


  • Open Access

    Measurement System and Testing Procedure for Characterization of the Conversion Accuracy of Voltage-to-Voltage and Voltage-to-Current Integrating Circuits for Rogowski Coils

    by Michal Kaczmarek

    Rogowski coils are increasingly being used in electricity metering systems. However, owing to their operating principle, they require an additional active integrating circuit to produce an output voltage or current that is directly proportional to the input current. A signal conditioner has the most significant impact on the overall conversion accuracy of the combined transducer. In this paper, a new measurement system and testing procedure utilizing a digital power meter and arbitrary waveform generator are proposed. This approach enables the characterization of the conversion accuracy of both types of active integrators: voltage-to-voltage and voltage-to-current converters. The conversion error for distorted input voltage harmonics and additional phase shift across a range of frequencies are determined. Instead of using the actual signal from the Rogowski coil during testing —which would be challenging owing to the required high RMS value of the distorted current for its input and difficulties in accurately measuring the RMS values of harmonics and their phase angles in relation to the output voltage or current of the tested converter—an arbitrary waveform generator is used. The input voltage to the active integrating circuit replicates the output voltage of the Rogowski coil: as the harmonic order increases, its RMS voltage rises proportionally.


  • Open Access

    Analytical Investigation of Primary Waveform Distortion Effect on Magnetic Flux Density in the Magnetic Core of Inductive Current Transformer and Its Transformation Accuracy

    by Michal Kaczmarek, Kacper Blus

    This paper analyzes how distortion in the primary current waveform affects the magnetic flux density in the magnetic core of an inductive current transformer and its transformation accuracy. Keeping the primary current’s RMS value constant, it studies the impact of changes in the RMS values and phase angles of low-order harmonics on the core’s flux density and the values of current error and phase displacement of their transformation. The distorted current waveforms, resulting flux density, and hysteresis loops are examined to identify the operating conditions of the inductive current transformer. This study also highlights the strong influence of low-order harmonics and the diminishing effect of higher-frequency harmonics on the magnetic flux density in its magnetic core, e.g., third, fifth, and seventh higher harmonics may cause an increase in magnetic flux density in the magnetic core of the inductive current transformer in relation to that obtained for a sinusoidal current with a frequency of 50 Hz by about 8.5%, while with additional second, fourth, and sixth harmonics, the increase may reach about 23%. Therefore, the testing procedure should consider not only the load impedance and the RMS values of the primary current but also its harmonic content, including the RMS values of individual harmonics and their phase angles.


  • Open Access

    Routine Testing–Oriented Method for Evaluating Inductive Current Transformers Accuracy Under Harmonic Distortion, Based on Maximum Current Error and Phase Displacement

    by Michal Kaczmarek

    In the case of the modern inductive current transformers the most important factor that have influence on their wideband accuracy is the self-distortion of the secondary current caused by the nonlinearity of the magnetization characteristic of the magnetic core. In response to the industry requirement to simplify the measuring procedure in this paper the idea is proposed to evaluate their transformation accuracy from tests made for increased frequency sinusoidal current with consideration of the impact of self-generated low-order higher harmonics. Moreover, this proposed method ensures simple and fast determination of the maximum values of current error and phase displacement for transformation of distorted current harmonics by inductive current transformers essential for accuracy class assessment. This is important due to the fact, that both the phase angles and the RMS values of higher harmonics depend on the source of disturbances in the power network and have significant influence on their transformation accuracy. Therefore, different results for different current distortion is possible and these multiple conditions should be considered for their reliable test of transformation accuracy for distorted currents. However, for accuracy class evaluation they are correctly represented by distorted waveform containing main component and single higher harmonics the maximum values of current error and phase displacement are determined. The presented analyses aim to justify the application of this simplified method for testing the transformation accuracy of inductive current transformers for harmonics of distorted currents in routine test in contrast to the full procedure required to be used in type test.


  • Precautionary Analysis of the Design Aspects of a Preventive Autotransformer to Eliminate its Potential Impact on the Results of DGA of Transformer Oil

    by Kacper Blus, Michał Kaczmarek, Grzegorz Drygała

    The article addresses the application of simulation and computer modeling using the Finite Element Method (FEM) to eliminate the potential impact of Preventive Autotransformer design on the results of Dissolved Gas Analysis (DGA) of transformer oil. The paper identifies critical design points of the preventive autotransformer that may contribute to gas emission. It details the potential impact of the construction and insulation system of high-current disc windings with multiple parallel groups. The uniformity of current distribution in the winding sections strongly depends on their placement relative to the core air gaps. The study presents the results of analyses on the impact of Preventive Autotransformer's winding and core air gaps design parameters on the current distribution and resulting temperature increases. The conclusions from the analyses indicate that design errors of Preventive Autotransformer windings can potentially affect DGA results, leading to the risk of incorrect assessment of the technical condition of power transformers. Furthermore, it is confirmed that precautionary analysis of the design aspects of the Preventive Autotransformer to exclude failures is justified and crucial for ensuring the accuracy and reliability of DGA measurements.

  • Open Access

    Operating Properties of the Inductive Current Transformer and Evaluation of Requirements for Its Compliance with the IEC 61869-1 WB2 Class Extension for Frequency up to 20 kHz

    by Michal Kaczmarek

    Nanocrystalline material provides an opportunity to improve the wideband performance of inductive current transformers and enables the possibility of ensuring their transformation accuracy for distorted and sinusoidal current from 50 Hz up to 20 kHz. Introduced in the year 2023, the standard IEC 61869-1 defines optional wideband accuracy classes for inductive current transformers with the WB2 class extension for harmonic frequencies up to 20 kHz. In this paper, design requirements in order to develop high accuracy 0.1-WB2 class wideband inductive current transformers compliant with the standards IEC 61869-1/2 are presented. It is shown that the main emphasis and design difficulties in ensuring high transformation accuracy still concern the lowest frequency of wideband operation—the fundamental component. However, it is of high importance that in order to obtain the highest possible wideband transformation accuracy of inductive current transformer for the low order higher harmonics, we ensure the lowest possible self-distortion of secondary current by minimalization of the load of its secondary winding is achieved—it should operate close to the short circuit conditions. Therefore, the low-power inductive CT should be designed and used for measurements in the power grid, as they will ensure the highest wideband transformation accuracy.


  • Open Access

    Nonlinearity of the magnetization characteristic of the magnetic core in calculation of current error and phase displacement values of inductive CTs

    by Michał Kaczmarek

    This paper explores the implications of employing a load exhibiting a power factor of 1 to test the transformation accuracy of an inductive current transformer with an apparent power below 5 VA. It offers an explanation of the change in current error and phase displacement correlates with the load power factor. The impact of the load power factor on the secondary winding on the accuracy of inductive CT is investigated in detail. The paper introduces a newly developed method that allows for the calculation of current error and phase displacement values for any power factor with consideration of the nonlinearity of the magnetization characteristic of the magnetic core. To ensure required accuracy of calculations of utmost significance is the potential RMS value modification of the magnetic core excitation voltage, which may further impact the transformation accuracy. Consequently, the operational conditions during the test are modified, and, owing to the nonlinearity of the magnetization characteristic of the magnetic core, the values of current error and phase displacement are also changed—not only due to a different load power factor connected to the secondary winding of the tested inductive current transformer. To maintain consistent operational conditions for a given secondary winding load power factor, the resistance connected to the secondary winding during the accuracy test with the power factor equal to 1 should be corrected. Moreover, the findings of this paper lead to the conclusion that evaluation of the transformation accuracy of inductive current transformer for both secondary winding load power factors is essential to ensure its reliable future operation in real conditions with the required accuracy class.


  • Open Access

    Development of Inductive Current Transformer 400/5/1 of Class 0.2S for Frequency Range 50 Hz–5 kHz

    by Michal Kaczmarek, Blazej Pacholczyk

    This paper is devoted to the development of a window-type inductive current transformer (iCT) with a rated primary current equal to 400 A and two secondary windings with rated currents of 5 A and 1 A. Its novelty concerns the presentation of this process in the case of an iCT with a 0.2S accuracy class ensured not only for a sinusoidal current of a frequency of 50 Hz but also for the transformation of distorted current in the harmonic frequency range from 50 Hz to 5 kHz. The maximum permissible values of the current error and phase displacement are equal to ±0.2% and ±0.2°, respectively, and are the same as the limiting values for a 50 Hz sinusoidal current of a rated RMS value. In the design process, three materials were considered for the construction of the developed iCT 400/5/1: electrical steel, permalloy and nanocrystalline (Nano). Their wideband properties were analyzed and the choice of the Nano magnetic core was justified with the already-available data in the literature on the basis of elaborated design assumptions. In order to specify its particular type, four magnetic cores with different initial magnetic permeabilities were tested. It was demonstrated that, as far as more favorable magnetic properties also involved increased active power losses in the magnetic core, it was not an appropriate choice for the construction of the iCT, especially for the transformation of the current with a main frequency equal to 50 Hz or 60 Hz.