Latest Publications

  • Transient Stability Analysis of Power-Synchronized PLL-Less Grid-Following Inverters

    by Milad Zarif Mansour, Nabil Mohammed, Mohammad Hasan Ravanji, Alireza Karimi, Behrooz Bahrani

    In the realm of modern power systems, grid-connected inverters are essential for integrating renewable energy resources. While grid-following inverters (GFLIs) currently dominate the market, grid-forming inverters (GFMIs) are pivotal for technology future power systems. Furthermore, recent research emphasizes the advantages of power-synchronized GFLIs (PSGFLIs), which combine the reliable operation of conventional GFLIs in strong grids with the stability of GFMIs in weak grids. This paper presents a comprehensive analysis of transient angle stability for a specific variant of PSGFLI, referred to as the linear parameter-varying control PSGFLI (LPV-PSGFLI). First, a nonlinear dynamic model suitable for transient stability analysis is derived. Then, the necessary and sufficient stability condition is obtained using Lyapunov's linearization stability analysis method. A method for estimating the required system variables for stability assessment is proposed, along with the static stability condition to identify the presence of an equilibrium point. Additionally, a Lyapunov energy function is proposed to determine the domain of attraction for the system's equilibrium point. The accuracy of the stability condition and the calculated domain of attraction is evaluated across multiple scenarios via simulations in MATLAB/Simulink and experimental tests performed on a scaled-down inverter experimentation platform.


  • Transient Stability of Paralleled Virtual Synchronous Generator and Grid-Following Inverter

    by Si Phu Me, Mohammad Hasan Ravanji, Milad Zarif Mansour, Sasan Zabihi, Behrooz Bahrani

    The majority of inverter-based resources (IBRs) currently operate as grid-following inverters (GFLIs). However, these inverters exhibit certain stability issues when integrated in low-strength areas of the grid. To enhance the grid strength in a GFLI-dominant area, virtual synchronous generators (VSGs) can be installed. If the VSG and the GFLI are investigated as a paralleled system, despite the benefits brought by the VSG, in some cases, the transient angle instability process, caused by a voltage sag, is accelerated, making the whole system more prone to instability. Therefore, this paper aims to study the transient angle stability of a paralleled VSG-GFLI system via investigating the voltage at a common bus between the two IBRs. Subsequently, a stable region of the voltage angles of the two IBRs is determined. Based on this stable region, the stability margin of the paralleled system can be determined and used to quantitatively evaluate the system stability. Moreover, an additional control loop is proposed to improve the transient stability of the paralleled system in this paper. The proposed controller can adaptively reduce the power set-point of the VSG to avoid a complete failure of the VSG even when no stable equilibrium point exists during a voltage sag. The stability investigation and performance evaluation of the proposed method are conducted in PSCAD/EMTDC and experimentally validated.


  • Impact of Voltage-Loop Feedforward Terms on the Stability of Grid-Forming Inverters and Remedial Actions

    by Mohammad Hasan Ravanji, Dayan B. Rathnayake, Milad Zarif Mansour, Behrooz Bahrani

    This paper reveals the impact of voltage control loop feedforward terms on the stability of grid-forming inverters (GFMIs) connected to a grid. By deriving a mathematical model, this paper shows that unless the GFMI current control loop is fast enough, the feedforward terms in the voltage control loop may threaten the GFMI small-signal stability. To this end, a necessary and sufficient condition for GFMI stability is proposed, provided that the grid impedance at the point of connection is known. Furthermore, two easy-to-implement yet effective remedial actions are proposed to enhance stability. Aiming to preserve the control structure, the first remedial action re-tunes the voltage controller to satisfy the obtained stability condition, while the second remedial action incorporates simple gains to attenuate the feedforward terms. Moreover, to demonstrate the effectiveness of the second remedial action, the obtained necessary and sufficient stability condition is modified to include the proposed attenuation gain. Eventually, the accuracy of the stability analysis and the effectiveness of the proposed remedial actions are evaluated in simulation and experiment.


  • Output Impedance Derivation and Small-Signal Stability Analysis of a Power-Synchronized Grid Following Inverter

    by Milad Zarif Mansour, Nabil Mohammed, Mohammad Hasan Ravanji, Behrooz Bahrani

    In recent years, grid-following inverters (GFLIs) and grid-forming inverters (GFMIs) have established their position as the mainstream synchronization techniques for the grid integration of inverter-based resources into power systems. However, both of these integration techniques have their shortcomings in weak, strong, and/or series-compensated grids. Recently, in the literature, a power synchronized GFLI has been proposed that does not suffer from the issues exhibited in GFLIs and GFMIs. This article provides an analytical output impedance of this power-synchronized GFLI that uses a linear parameter-varying controller (LPV-PSGFLI). This impedance is then used for impedance-based stability analysis via the Nyquist stability criterion. In addition, the derived impedance is validated via system identification, and a comparison between a conventional GFLI and an LPV-PSGFLI is made under various system strengths. It is seen that the LPV-PSGFLI can inject power into the grid, whereas the conventional GFLI fails when both are integrated into a very weak grid. Finally, the accuracy of the impedance-based stability analysis using the derived output impedance is validated in Matlab/PLECS and in experiments in various scenarios.


  • Linear Parameter-Varying Control of a Power-Synchronized Grid-Following Inverter

    by Milad Zarif Mansour, Mohammad Hasan Ravanji, Alireza Karimi, Behrooz Bahrani

    This article proposes a linear parameter-varying loop-shaping controller for a power-synchronized grid-following inverter (PSGFLI). This control strategy regulates the inverter output active and reactive powers at the terminal instead of the point of connection and does not require a phase-locked loop (PLL) for extracting the voltage phase angle. Hence, the prevalent stability issues exhibited when GFLIs are connected to weak grids are not present, and the proposed PSGFLI control strategy can work under both very weak and strong grid conditions without being prone to instability. In this approach, the controller parameters are functions of the operating point and are changed during the real-time operation such that the closed-loop performance is preserved in all operating points. Furthermore, since the grid impedance is a factor in the design process, a robustness analysis against grid impedance estimation error is conducted, and it is shown that discrepancies in the estimated and real grid impedances are unlikely to make the system unstable. The performance of the proposed control design is validated in MATLAB/PLECS and experiments for both strong and weak grids.


  • Small-Signal Synchronization Stability Enhancement of Grid-Following Inverters via a Feedback Linearization Controller

    by Milad Zarif Mansour, Mohammad Hasan Ravanji, Alireza Karimi, Behrooz Bahrani

    This paper proposes a feedback linearization controller for a grid-following inverter (GFLI) that uses a conventional Phase-Locked Loop (PLL) as the synchronization unit. The proposed controller enhances the GFLI synchronization by expanding the PLL domain of attraction to the whole plane that is limited to a small region around the equilibrium point in a conventional PLL, provided that the grid impedance and voltage are known. Linearizing the overall closed-loop system, the proposed controller provides linear system attributes for the PLL, leading to an infinite domain of attraction and only one equilibrium point. Additionally, a state-feedback controller is integrated within the feedback linearization controller so that it enables the system to have an adjustable dynamic response. Finally, it is shown that the system is robust against parametric uncertainties. The performance of the proposed control design is validated in Matlab/Simulink and experiment. It is verified that the proposed controller expands the domain of attraction and enhances the system dynamic response.


  • Open Access

    Linear Parameter-Varying Control of A Power-Synchronized Grid-Following PLL-Less Inverter

    by Milad Zarif Mansour, Alireza Karimi, Behrooz Bahrani

    This paper proposes a Linear Parameter-Varying loop-shaping controller for a power-synchronized Phase-locked Loop (PLL)-less grid-following inverter (GFLI). This control strategy regulates the inverter's output active and reactive powers at the terminal instead of the point of connection and does not require a PLL for extracting the voltage phase angle. Hence, the prevalent stability issues exhibited when GFLIs are connected to weak grids are not present, and the proposed GFLI control strategy can work under both very weak and strong grid conditions without being prone to instability. In this approach, the controller parameters are functions of the operating point and changed during the real-time operation such that the closed-loop performance is preserved in all operating points. Furthermore, since the grid impedance is a factor in the design process, a robustness analysis against grid impedance estimation error is conducted, and it is shown that discrepancies in estimated and real grid impedances are unlikely to make the system unstable. The performance of the proposed control design is validated in Matlab/PLECS and experiment for both strong and weak grids.

  • Top Cited Papers

    Nonlinear Transient Stability Analysis of Phased-Locked Loop-Based Grid-Following Voltage-Source Converters Using Lyapunov’s Direct Method

    by Milad Zarif Mansour, Si Phu Me, Sajjad Hadavi, Babak Badrzadeh, Alireza Karimi, Behrooz Bahrani

    In this article, using Lyapunov’s stability theorem, the transient stability conditions for a grid-following voltage-source converter (VSC) are found. These conditions take into account both the grid specifications and the VSC’s dynamics. The derived conditions are based on a well-known nonlinear model of the VSC’s phase-locked loop. To evaluate the stability of the nonlinear system, Lyapunov’s direct method is employed. To this end, a new Lyapunov’s function is proposed, and its characteristics are analyzed. Using this Lyapunov’s function, the domain of attraction of the system’s equilibrium point is calculated. In addition, a novel system strength index based on the domain of attraction of the system is proposed. The privileges of this index over the conventional indices are absoluteness, VSC’s dynamics consideration, and comparability of different VSCs with each other from a stability point of view. In the end, the correctness of the proposed stability analysis is validated via simulation in MATLAB/PLECS and experiment.


  • Optimal Allocation and Sizing of Synchronous Condensers in Weak Grids With Increased Penetration of Wind and Solar Farms

    by Sajjad Hadavi, Milad Zarif Mansour, Behrooz Bahrani

    The increasing number of weak-grid-connected renewable energy resources in power systems has created various challenges in recent years. Some examples include un-damped voltage oscillations in the ERCOT and sub-synchronous resonance in the North-China power grid. Several solutions for these challenges have been proposed, such as Static Compensators and Synchronous Condensers (SynCons). SynCons, being synchronous machines without a prime mover, provide several benefits in weak power systems, such as frequency support, system strength, and voltage regulation. Although SynCons are widely-utilized to mitigate the weak grid integration challenges, their installation/operation costs make them a costly solution. Additionally, their lead-time can be more than a year, which means their initial sizing and allocation must be optimal. In this paper, a method for the optimal allocation and sizing of SynCons is proposed. The main objective of this method is maintaining Short Circuit Ratio (SCR) in the system greater than pre-defined values while the investment and operation costs of SynCons, and voltage deviation in the system are minimized. Three meta-heuristic optimization algorithms are used to implement the proposed method, and its performance is evaluated via Electromagnetic Transient (EMT) time-domain simulation in a modified IEEE 39-bus system. The PSCAD/EMTDC software is used for the time-domain simulation. The simulation results confirm that with optimized allocation and sizing, the SCR of the network in all areas is more than pre-defined values, and also, all renewable energy resources can ride through disturbances and comply with given grid codes.