Current Organizations / Institutes

The organizations/institutes from the scholar's latest article


Ze Guo has a total of 34 co-authors. Here are the top co-authors by number of shared publications:

  • Hang Liu

    State Key Laboratory of Reliability and Intelligence of Electrical Equipment, Hebei University of Technology 1 , Tianjin 300130

    3 shared publications
  • Zixu Guo

    State Key Laboratory of Reliability and Intelligence of Electrical Equipment, Hebei University of Technology 1 , Tianjin 300130, China

    3 shared publications
  • Chuanjun Ma

    State Key Laboratory of Reliability and Intelligence of Electrical Equipment, Hebei University of Technology 1 , Tianjin 300130, China

    2 shared publications
  • Xiaozhen Zhao

    State Key Laboratory of Smart Power Distribution Equipment and System, Hebei University of Technology, Tianjin 300401, China

    2 shared publications
  • Boya Zhang

    State Key Laboratory of Electrical Insulation and Power Equipment Xi'an Jiaotong University Xi'an China

    1 shared publication
  • Chen Ma

    State Key Laboratory of Reliability and Intelligence of Electrical Equipment, Hebei University of Technology 3 , Tianjin 300130, China

    1 shared publication

Latest Publications

  • Residual Magnetism Elimination Method for Large Power Transformers Based on Energy Storage Oscillation

    by Xiaozhen Zhao, Haodong Wu, Dingqian Yang, Junyi Wei, Zhipeng Li, Ze Guo, Shuo Zhang

    Power transformers are crucial components that contribute to the overall stability and reliability of the power grids. Due to hysteresis effects, residual magnetism can remain in the transformer’s iron core after switching off. This residual magnetism can cause excitation inrush when the transformer is re-energized, potentially damaging the transformer, threatening grid stability, and increasing the risk of power grid failure. To address this issue effectively, a universal, reliable, and fast method for eliminating residual magnetism is needed. This paper proposes an energy storage oscillation method for eliminating remanent magnetization in large power transformers. The method’s effectiveness and speed are validated through simulations and experimental comparisons with various demagnetization techniques. The results confirm that this method is not only rapid but also highly effective in practical applications.


  • Open Access

    Research on dynamic ablative behavior of contact during breaking of DC circuit breaker

    by Ze Guo, Chuanjun Ma, Zixu Guo, Hang Liu, Xiangji Chen

    During the circuit breaker’s breaking process, an arc is generated, which exerts an ablative effect on the contacts and significantly impacts the electrical life of the circuit breaker. Therefore, studying the ablation mechanism of arcs is crucial for enhancing the breaking performance and extending the electrical life of circuit breakers. To investigate the ablation effect of arcs on contacts, a double-break DC circuit breaker model was developed. Utilizing magnetohydrodynamics theory, FLUENT software was employed to simulate the arc motion, establish the energy balance equation for arcing and contacts, analyze the ablation mechanism during arc ignition, and calculate the mass loss of contacts during a single arc event. An experimental platform was established to conduct electrical life tests on the circuit breaker. The ablation mass loss was measured through these tests. The results indicate that under identical breaking conditions, the experimental outcomes align with the simulation results. Building on this, the influence of the breaker’s breaking speed on contact ablation was examined. Simulation results reveal that the arc ablation at the end of the contact is most severe during the combustion process, and as the breaking speed increases, the extent of arc ablation on the contact gradually diminishes.


  • Open Access

    Simulation of auto-expansion high voltage SF6 circuit breaker breaking process considering valve motion

    by Ze Guo, Weimeng Han, Zixu Guo, Hang Liu, Chuanjun Ma

    High voltage circuit breakers are important equipment in power systems, and the valve motion of the chambers plays a role in the arc extinguishing performance of high-voltage circuit breakers. Therefore, in this paper, a 145 kV auto-expansion SF6 circuit breaker is taken as the research object, and a two-dimensional axisymmetric magnetohydrodynamic arc model considering valve motion process is established. The influence of different short circuit breaking conditions on the valve motion was studied. The results show that the backflow phenomenon of ablated steam is the main reason for the closure of the non-return valve, which plays an important role in opening the pressure relief valve. The closing time of the non-return valve is about 0.4 ms faster at a short circuit current of 40 kA than at a short circuit current of 36 kA.


  • Open Access

    Effect of aluminum particles on the insulating properties of C4F7N/CO2 mixed gas

    by Ze Guo, Min Li, Zixu Guo, Chuanjun Ma, Hang Liu

    The C4F7N/CO2 mixed gas is most expected to replace SF6 in high-voltage power equipment, and the generation of free metal particles in gas-insulated equipment is unavoidable and highly susceptible to inducing insulation failures. In this paper, the effects of flaky, spherical, and mixed shape aluminum particle defects on the breakdown characteristics of C4F7N/CO2 mixed gas are investigated and compared to those of SF6 under the same conditions. The experimental results show that the effect of particle defects on the insulating properties of C4F7N/CO2 gas mixtures is visualized by the fact that particle defects reduce the breakdown voltage of C4F7N/CO2 gas mixtures, increase their stochasticity, and reduce the enhancement of the insulating properties of C4F7N/CO2 gas mixtures by increasing the air pressure. The greater the number of particles, the greater is the degree of influence. Comparison of the SF6 and C4F7N/CO2 gas mixtures reveals that, in the case of flake defects, increasing the air pressure improves the insulation performance of the SF6 gas better than that of the C4F7N/CO2 gas mixture. Under the condition of the same number of particles, the larger the proportion of spherical particles in the hybrid particles, the smaller is the influence of metal particles on the C4F7N/CO2 mixed gas and on SF6 gas.


  • Open Access

    Simulation study on arc motion process of 38 A low-voltage AC contactor under AC-4 conditions

    by Chen Ma, Shiwei Ge, Hongwei Zhang, Xinhua Ji, Zhenkun Wang, Ze Guo

    In the process of breaking an AC contactor, the ablation of the contact by the arc current is an important factor affecting its electrical life, so the evolution of arc shape in the arc extinguishing chamber has an important influence on its breaking performance. To explore the influence of arc motion characteristics on its breaking characteristics, based on the theory of magnetohydrodynamics and considering the contact motion process, a three-dimensional air arc simulation model is established for the arc extinguishing chamber of an AC contactor with a fixed current of 38 A and the arc motion characteristics of the arc during breaking are analyzed. To verify the accuracy of the simulation model, a test platform was built. Under the same breaking conditions, the arc shape, arc voltage, and arc current were measured, and the experimental results were consistent with the simulation results. On this basis, an optimization scheme of the arc extinguishing component is proposed and its influence on the arc motion process is analyzed.


  • Open Access

    Effect of nucleating agents on the electrical properties of cross‐linked polyethylene under tensile stress

    by Yunqi Xing, Jiahao Liu, Jingang Su, Junwei Zha, Guochang Li, Ze Guo, Xiaozhen Zhao, Mengjia Feng

    During the operation of high‐voltage cables, external stress and residual stress can affect the aggregated structure of insulating materials and lead to significant deterioration in their electrical performance. To investigate the evolution characteristics of the electrical properties of cross‐linked polyethylene (XLPE) under mechanical stress, this paper explains the relationship between the aggregated structure of XLPE and its electrical properties and proposes a method for improving insulation performance under mechanical stress. The results show that metallocene polyethylene used as a nucleating agent can promote crystallisation through heterogeneous nucleation and increase Young's modulus by non‐uniform nucleation, increasing crystallinity and reducing interplanar spacing, resulting in more complete crystal forms and reduced damage to the aggregated structure during the tensile process. After nucleating agent modification, the XLPE crystallisation becomes more uniform, and interfacial adhesion forces increase. The weakened interface damage process between the amorphous and crystalline regions under tensile stress effectively inhibits the process of molecular chain polarisation turning and reduces trap density. The modified XLPE crystal structure shows a tendency towards densification and enhanced molecular chain interactions, which can reduce the damage to the aggregated structure under tensile stress, while the reduced free volume inside the material and the shortened average free path of carriers can weaken the damage of high‐energy electrons to molecular chains, thereby inhibiting the process of electrical tree degradation. The results show that nucleating agents have great potential for maintaining the stable operation of XLPE cables under mechanical stress.


  • Open Access

    SF6 High-Voltage Circuit Breaker Contact Status Detection at Different Currents

    by Ze Guo, Linjing Li, Weimeng Han, Zixuan Guo

    Currently, the online non-destructive testing (NDT) methods to measure the contact states of high-voltage circuit breakers (HVCBs) with SF6 gas as a quenching medium are lacking. This paper aims to put forward a novel method to detect the contact state of an HVCB based on the vibrational signal. First, for a 40.5-kV SF6 HVCB prototype, a mechanical vibration detection system along with a high-current generator to provide the test current is designed. Given this, vibration test experiments are carried out, and the vibration signal data under various currents and corresponding contact states are obtained. Afterward, a feature extraction method based on the frequency is designed. The state of the HVCB contacts is then determined using optimized deep neural networks (DNNs) along with the method of adaptive moment estimation (Adam) on the obtained experimental data. Finally, the hyperparameters for the DNNs are tuned using the Bayesian optimization (BO) technique, and a global HVCB contact state recognition model at various currents is proposed. The obtained results clearly depict that the proposed recognition model can accurately identify five various contact states of HVCBs for the currents between 1000 A and 3500 A, and the recognition accuracy rate is above 96%. The designed experimental and theoretical analysis in our study will provide the references for future monitoring and diagnosis of faults in HVCBs.


  • Arc Interruption Performance of C4F7N-CO2 Mixture in a 126 kV Disconnector

    by Boya Zhang, Ran Zhou, Kai Wang, Ze Guo, Xingwen Li, Minchuan Cao, Junwei Deng, Dibo Wang

    The C 4 F 7 N-CO 2 mixture is considered the most promising alternative gas to SF 6 in high voltage power apparatuses. This paper demonstrates the feasibility of using C 4 F 7 N-CO 2 as an SF 6 alternative to switch the current in a 126 kV disconnector. Firstly, the insulation performance of the mixture of C 4 F 7 N and CO 2 was investigated and the appropriate fraction of the C 4 F 7 N-CO 2 gas mixture was found to be 5% by taking the limitation of minimum operating temperature into account. Secondly, the arc interruption capability of C 4 F 7 N-CO 2 and SF 6 were compared. The arcing process of the bus-transfer current interruption was evaluated based on the magneto-hydro-dynamics (MHD) arc model. For the small inductive current interruption, the dielectric recovery properties were analyzed. In particular, the dielectric recovery strength of the C 4 F 7 N-CO 2 during the post-arc phase was calculated based on the streamer inception criterion. Finally, the interruption experiments and type tests further verified the feasibility of the C 4 F 7 N-CO 2 in the disconnector. The investigation in this paper demonstrates that the C 4 F 7 N-CO 2 mixture can be used in the 126 kV disconnector to replace SF 6 .