Study on the Failure Causes and Improvement Measures of Arresters in 10 kV Distribution Transformer Areas
Open Access
Abstract
In recent years, arresters in 10 kV distribution transformer areas of the Guangdong power grid have exhibited a rising trend of premature failures, posing a serious threat to distribution network reliability. This paper studied the failure causes of arresters through performance tests on failed arresters and through deterioration tests on new arresters and their prorated sections under typical operating stresses. The failed arresters and their internal varistors displayed varying degrees of physical damage and pronounced degradation in electrical performance, characterized by a strong polarity effect on the DC reference voltage (U1mA), elevated DC leakage current (IL) and resistive current (iR), and excessive residual voltage (U5kV). In the lightning impulse test, varistors primarily showed pinhole-type damage and significant polarity effects on ΔU1mA. In the AC aging test, ΔU5kV increased markedly. In the water immersion test, varistors exhibited salt deposits and aluminum electrode blackening, with ΔU1mA decreasing, while IL and ΔiR increased significantly. Overall, internal moisture superimposed on other operating stresses was identified as a major internal cause of arrester failure, while pollution flashover of the housing was considered the primary external factor. Corresponding improvement measures in material optimization, testing and inspection, and operation and maintenance are proposed to enhance arrester reliability.Keywords
Funding Information
- National Engineering Research Center of UHV Technology and Novel Electrical Equipment Basis (NERCUHV-2023-KF-12)
This publication has 24 references indexed in Scilit:
- Surge arrester optimal placement in distribution networks: A decision theory-based approachElectric Power Systems Research, 2024
- Study of the Effect of Ca on the Electrical Properties of SnO2 Varistor Based on the Voronoi ModelJournal of Electronic Materials, 2024
- Short duration current impulse waveform effects on the degradation and energy absorption capability of zinc oxide varistorsElectric Power Systems Research, 2023
- Lightning Protection of Distribution Power Systems: Arrester Development and Application Over the YearsIEEE Power and Energy Magazine, 2023
- High improvement of degradation behavior of ZnO varistors under high current surges by appropriate Sb2O3 dopingJournal of the European Ceramic Society, 2021
- Limiting surge arrester failure under direct lightning strokes for attaining service continuity of distribution networksIET Generation, Transmission & Distribution, 2020
- AC ageing characteristics of Co-doped ZnO varistorsScience China Technological Sciences, 2013
- TSC characteristics of AC aged ZnO varistorsScience China Technological Sciences, 2013
- Non-uniform ageing behavior of individual grain boundaries in ZnO varistor ceramicsJournal of the European Ceramic Society, 2011
- Voltage distribution studies on ZnO arrestersIEE Proceedings - Generation, Transmission and Distribution, 2002