Online Split-Phase Identification of Asymmetric Parameters Between Distribution Lines and Ground for Unbalanced Voltage Compensation Based on Power Electronics
- 2 May 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 39 (8) , 10067-10078
Abstract
Most of the phase-to-ground parameters induced between distribution lines and ground are asymmetric, which can result in the generation of unbalanced voltage, shifting the neutral point voltage. For compensated distribution networks, the existence of an arc suppression coil can increase the influence of asymmetric parameters and exacerbate the deviation of neutral point voltage. Maintaining the balance of three-phase voltage is not only a prerequisite for the stable operation of the distribution networks, but also for improving the reliability of single-phase ground fault detection. This paper proposes a novel online split-phase identification of asymmetric parameters between distribution lines and ground for unbalanced voltage compensation based on power electronics. Firstly, an adaptive active current-type compensation method based on power electronics is proposed, it can adapt to compensate for threephase unbalanced voltage with different neutral point grounding styles. Secondly, particle swarm optimization is used to realize the online split-phase identification of the phase-to-ground parameters of the distribution power lines. The identified parameters are used to calculate the reference value of the compensation current and the asymmetry of each phase-toground parameter. Finally, the feasibility and effectiveness of the proposed method are verified by simulation and experiment.Keywords
Funding Information
- National Natural Science Foundation of China (51677030)
- Natural Science Foundation of Fujian Province, China (2023J05106)
This publication has 28 references indexed in Scilit:
- Application of semantic segmentation in High-Impedance fault diagnosis combined signal envelope and Hilbert marginal spectrum for resonant distribution networksExpert Systems with Applications, 2023
- Suppression Strategy on Neutral Point Overvoltage in Resonant Grounding System Considering Single Line-to-ground FaultElectric Power Systems Research, 2022
- A novel method of insulation parameters measurement based on hybrid flexible arc suppression device in distribution networksInternational Journal of Electrical Power & Energy Systems, 2021
- Single-phase flexible arc suppression device based on BSC-SOGI-PLL method for distribution networksInternational Journal of Electrical Power & Energy Systems, 2020
- Phase-Ground Fault Current Analysis and Protection of a High-Resistance Grounded Power SystemIEEE Transactions on Industry Applications, 2020
- Deep-Learning-Based Earth Fault Detection Using Continuous Wavelet Transform and Convolutional Neural Network in Resonant Grounding Distribution SystemsIEEE Sensors Journal, 2017
- Methods of unbalanced voltage control in nonsolidly grounded systems based on current injectionInternational Transactions on Electrical Energy Systems, 2016
- Capacitor placement in distribution systems for power loss reduction and voltage improvement: a new methodologyIET Generation, Transmission & Distribution, 2016
- Principle and Design of a Single-Phase Inverter-Based Grounding System for Neutral-to-Ground Voltage Compensation in Distribution NetworksIEEE Transactions on Industrial Electronics, 2016