Intrinsically Safe Grounding Systems and Global Grounding Systems
- 22 August 2017
- journal article
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 54 (1) , 25-31
Abstract
This paper introduces a characterization of a single Grounding System (GS) or a set of interconnected GSs, according to their safety level and defines their condition of “conventionally safe” and “intrinsically safe”. GSs or a set of them are intrinsically safe, if they guarantee safe touch/step voltages permanently permissible for an assigned ground fault value. It is proposed a new definition of Global Grounding Systems (GGSs) revising that offered by the Standards IEC 61936-1/EN 50522. The paper suggests a safety criterion, useful for urban and industrial areas with reduced accessibility, that allows identifying the safety zone of influence and the intrinsically safe condition of a single GS and of a GGS, constituted by a set of interconnected single GSs.Keywords
This publication has 14 references indexed in Scilit:
- Tests and Monitoring of Grounding Systems in HV/MV SubstationsIEEE Transactions on Industry Applications, 2016
- The identification of global earthing systems: A review and comparison of methodologies2016
- On the effects of HV/MV stations on global grounding systems2016
- Single grounding system intrinsically safe and global grounding system safe as set2016
- Global earthing systems: Characterization of buried metallic parts2016
- Currents Distribution During a Fault in an MV Network: Methods and MeasurementsIEEE Transactions on Industry Applications, 2016
- Identification of Global Grounding Systems: The Global Zone of InfluenceIEEE Transactions on Industry Applications, 2015
- Needs of Management of the Grounding SystemsIEEE Transactions on Industry Applications, 2015
- Impact of MV Ground Fault Current Distribution on Global Earthing SystemsIEEE Transactions on Industry Applications, 2015
- Analysis of interconnected earthing systems of MV/LV substations in urban areas2008